Conductivity Controls Sensitivity vs. Maximum Probe Wire Distances

 

Sensitivity vs. Maximum Probe Wire Distances - in feet*

Notes:

  1. DC on probe circuit-maximum distance between control and probe is limited to the total resistance of the wire and liquid.
  2. Total resistance must not exceed the sensitivity of the control.
  3. On controls directly connected to floats rather than probes, maximum distance is limited only to the total resistance of the wire.
  4. AC probe circuit has greater restrictions on maximum distance.

*Based on type MTW or THHN #14 or #16 AWG wire. Other wire size and sensing medium may reduce overall maximum distance.

 

OhmsSeries
16, 16D, 16M, 16DM, 16VM
Series
17
Series
27
Series
47
Series
67
Series
26, 26M
Series
19MR
Series
DF
3,000----4000----------
3,300--5000------------
4,700100003500----4000900--900
1000057001750900--2400600--600
11,000------------5500--
19,000------------3000--
22,000--1000------------
26,0002200----15001200250--250
47,000--500------------
50,0001075----900600------
100,00057025075----------
470,000270--------------
1,000,00038----400300------

 

For Ohms 3,000,000 & 5,500,000, Contact Factory for more information.